Signatrol SL709 - Dual Channel Pulse Input Data Logger


The SL709 is a dual channel pulse data logger. The SL709 is commonly used to measure the switch output from flowmeters although it can be used as a standard pulse counter. The SL709 will count up to 4096 counts in the predefined sample period. The SL709 can be connected direct to switches, or volt free contacts as well as electrical signals where the low level is less than 0.5VDC and the high signal is between 4.5VDC and 24VDC. As with all SL700 series data loggers, they are supplied with an internal battery giving up to 10 years battery life.
Specifications:

Internal battery (10 year life)
Temperature Range -40°C to +70°C
Two channels
Voltage: Low = <+0.5VDC High = >+4.5 to +24VDC
Accuracy ±1 Pulse / Sample Period
Number of Readings: 21,500 - 87,000
Sample 8 seconds to 8 hours
Readings 25/sec using optional battery pack